dc.titleReliability of automatic sprinkler systems in shopping centres in Hong Kongen_US
dcterms.abstractShopping centres have been very popular in Hong Kong in the past two decades. Sprinkler systems became mandatory for shopping centres in 1973. However, some sprinkler systems may not be maintained properly, especially in those small shopping centres managed by small property management companies. Furthermore, the sprinkler systems are often regarded as if they can function effectively even without any maintenance. As a result, many sprinkler systems installed in shopping centres have become antiquated and are poorly maintained. Their effectiveness in fire extinguishment is in doubt. The reliability of automatic wet pipe sprinkler systems in shopping centres was studied and analyzed with the aid of the fault tree analysis technique. A mathematical model was developed from the fault tree diagram to estimate the average statistical downtime of sprinkler systems. The study is carried out to identify the weak areas of typical wet pipe sprinkler systems and to ascertain if the sprinkler systems installed in the shopping centres in Hong Kong are as effective as they are perceived by the general public. Designs of most wet pipe sprinkler systems are similar. A typical schematic diagram is produced for the purpose of analysis. The major components of the system are identified and their failure modes are defined. The fault tree analysis technique is used to develop a fault tree and subsequently, a mathematical model for this generic system. The mathematical model is a useful tool for analysis because the mean fractional dead time or the average statistical time when the system is in failed state, can be estimated by inserting the respective failure rates of the components and sub-systems of the sprinkler system into the mathematical equation. It is found that the system shutdown rate, which may be caused by maintenance or repair of the system components, has the greatest impact on the overall system failure probability. The system is less susceptible to the failure of other components such as the sprinkler pumps and the emergency generator because of the redundancy arrangement in these sub-systems. The conclusion conforms to findings in the literatures that water being shut-off is the main cause of failure of sprinkler system. The effect of the shutdown duration on the overall system failure probability is explored and corresponding measures are recommended in this study. To conclude, automatic sprinkler systems are not maintenance-free systems. Instead, they require close attention and proper maintenance in order to be effective and reliable in fire extinguishment.en_US
dcterms.extentxii, 87, [51] leaves : ill. (some col.) ; 31 cmen_US
dcterms.isPartOfPolyU Electronic Thesesen_US
dcterms.issued1999en_US
dcterms.educationalLevelAll Masteren_US
dcterms.educationalLevelM.Sc.en_US
dcterms.LCSHFire sprinklers -- China -- Hong Kongen_US
dcterms.LCSHFire sprinklers -- China -- Hong Kong -- Mathematical modelsen_US
dcterms.LCSHShopping malls -- Fires and fire prevention -- China -- Hong Kongen_US
dcterms.LCSHHong Kong Polytechnic University -- Dissertationsen_US
dcterms.accessRightsrestricted accessen_US

Files in This Item:
File Description SizeFormat 
b14719010.pdfFor All Users (off-campus access for PolyU Staff & Students only)7.74 MBAdobe PDFView/Open


Copyright Undertaking

As a bona fide Library user, I declare that:

  1. I will abide by the rules and legal ordinances governing copyright regarding the use of the Database.
  2. I will use the Database for the purpose of my research or private study only and not for circulation or further reproduction or any other purpose.
  3. I agree to indemnify and hold the University harmless from and against any loss, damage, cost, liability or expenses arising from copyright infringement or unauthorized usage.

By downloading any item(s) listed above, you acknowledge that you have read and understood the copyright undertaking as stated above, and agree to be bound by all of its terms.

Show simple item record

Please use this identifier to cite or link to this item: https://theses.lib.polyu.edu.hk/handle/200/1683