dc.title | Radiant heat and respiratory droplet distribution with stratified air distribution system | en_US |
dcterms.abstract | Stratified air distribution systems such as Displacement Ventilation (DV) and Under-Floor Air Distribution (UFAD) systems proved to provide better indoor air quality compared with Traditional Mixing Ventilation (MV) system. Furthermore, radiant heat and respiratory droplet in an enclosed space are regarded as critical factors respectively related to energy efficiency and indoor air quality. Different air distribution systems have their own characteristics of the distribution of respiratory droplet, and affects the spatial actual cooling load in UFAD systems. This study investigates the distribution of radiant heat which is generated from human body and the respiratory droplet with the size varied from 0.1um to 10um in the room installed with Displacement Ventilation system. In addition, the convective heat is also analyzed to compare with the radiant heat in this case. A stainless steel chamber installed with air-conditioning system was supplied to conduct the experiment for this research. Two thermal manikins and some basic office equipments were placed in the chamber to simulate the circumstance of a real office. The flow rate of supply air was controlled around 0.2m/s which was coincided with displacement ventilation system. That manikin produced heat by winding around heating wire according to the value of real person. The aerosols were produced by Ions generator to imitate the respiratory droplet. Multiple measuring points were set on vertical, horizontal and nostril area to obtain the concentration distribution of particles with different diameters under Displacement Ventilation system. Lots of previous researches have studied on the case that only one person seated in the room. This paper aims to find out the results of radiant heat distribution when two persons are working in the room simultaneously. From the experiment data, it can be observed that the radiant heat of the lower zone is slightly larger than that in the upper zone generally. The distribution radio of radiant heat and convective heat are related to the velocity and temperature of the air in the chamber. The conclusions also indicate the aerosols are easily trapped in the middle-height of the room which disobeys the general two-zone theory of the DV system. Due to the limitations of this study, the current results only provide a first attempt to perform basic analysis. The precision of the experiments can be enhanced in the future study to obtain a more powerful and representative results which can be applied to improve the indoor air quality. | en_US |
dcterms.extent | x, 67 leaves : ill. (some col.) ; 30 cm. | en_US |
dcterms.isPartOf | PolyU Electronic Theses | en_US |
dcterms.issued | 2011 | en_US |
dcterms.educationalLevel | All Master | en_US |
dcterms.educationalLevel | M.Eng. | en_US |
dcterms.LCSH | Air conditioning. | en_US |
dcterms.LCSH | Stratified flow. | en_US |
dcterms.LCSH | Heat -- Radiation and absorption. | en_US |
dcterms.LCSH | Indoor air pollution. | en_US |
dcterms.LCSH | Air quality management. | en_US |
dcterms.LCSH | Displacement ventilation. | en_US |
dcterms.LCSH | Hong Kong Polytechnic University -- Dissertations | en_US |
dcterms.accessRights | restricted access | en_US |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
b24497927.pdf | For All Users (off-campus access for PolyU Staff & Students only) | 32.17 MB | Adobe PDF | View/Open |
Copyright Undertaking
As a bona fide Library user, I declare that:
- I will abide by the rules and legal ordinances governing copyright regarding the use of the Database.
- I will use the Database for the purpose of my research or private study only and not for circulation or further reproduction or any other purpose.
- I agree to indemnify and hold the University harmless from and against any loss, damage, cost, liability or expenses arising from copyright infringement or unauthorized usage.
By downloading any item(s) listed above, you acknowledge that you have read and understood the copyright undertaking as stated above, and agree to be bound by all of its terms.
Please use this identifier to cite or link to this item:
https://theses.lib.polyu.edu.hk/handle/200/6409